1User’s ManualUNINTERRUPTIBLE POWER SUPPLYR
10 2 INSTALLATION 2.1 Environment Selection ◆Working Temperature:0-40℃ ◆Storage Temperature:-40-70℃(without battery) -20-55℃(with battery) ◆Relative
11 included and if the real product is right. 2.3.1 Accessories User manual, 1pc; CD for monitoring software, 1pc; Cables for RS232 and USB interfa
12 RS232USBEPO(Emergency Power OFF)fanParallel PortOutput BreakerManual Bypass BreakerAC BreakerBypass BreakerBattery BreakerIntelligent SlotFront Pa
13 15 380 220 94 68 125 100 20 380 220 122 90 150 125 30 380 220 177 136 200 160 Note: Forbid to use creepage protection type switc
14 2.7 Installation instruction of single unit E L-+EN JP1 JP2 L N Figure2.5 Single phase 4~10K terminal connection drawing Figure2.6 three phase in
15 2.8.2 Cable connection of hot standby NLJP2JP1N E+ -LEE L-+EN JP1 JP2 L NSlave UPS Master UPSAC input Battery1 Battery2 Load Figure2.8 Single phas
16 the slave UPS works at “0” load status.Once the master UPS is failed,the master will transfer to bypass and then the slave UPS provides the power
17 All UPS switches are at off mode. 3.2 Starting steps of single UPS. Turn the input AC switch.The power supply board starts to work and the LCD w
18 3.7 Maintenance operation steps This steps must be done by pforessional people, otherwise it’s accounto your responsibility for any cost. Turn o
19 (5)Inverter output indicator (green).It will light when the Inverter is working and outputing. (6)Error alarm indicator (red).It will light with a
2 Caution Please strictly comply with the manual operation instruction, and keep the manual well. Make sure to read the manual carefully before use!
20 If you don’t select the language the language, the system will set the language as Chinese automatically, and enter “Sleep” model. 2) Press the
21 6)Select “output parameter” and press “enter” to check the parameter of output. 7)Press “ESC”, the window will be back to last page, select “mo
22 9)Or you may check the voltage of the DC wire inside UPS 10)Press “ESC” to return to the last step,press “Input the parameter”and “Enter”to chec
23 RS485.It communicates one by one thru RS232. It has remote communication thru RS485.There is built-in SNMP card (optional) to complete remote alar
24 5.6 EPO interface EPO completes remote turn off urgently. When UPS does working, EPO are under short circuit. When EPO is open, UPS closes output.
25 2) Please warn high voltage inside the UPS the time of day.And keep no power inside the UPS before maintenance. 3) Stop to take metal, jewelry,wat
26 6.5 package, shippment and storage. 6.5.1 package There are two packages. Firstly we use carton to pack them. Then we will use wooden carton to pa
3 Content 1 SYSTEMS ... 5 1.1 BRIEF
4 5.1 RS232 instructions ...23 5.2 RS485 Instructions ...
5 1 SYSTEMS 1.1 BRIEF INTRODUCTION DSP series UPS are mainly applied to computers, data center, administration center of networks, precision instrume
6 voltage by PFC. The contactor pull in only when the DC Bus voltage reach upto a certain value. The battery supply DC power to inverter via the PFC
7 Figure 1.2,When AC is abnormal or inverter failure, the UPS input rectifier is off and the DC power from battery is supplied to inverter through st
8 switch, ouput switch and battery switch and then the UPS is transferred to maintenance working mode, see the arrow in the figure; it is safe to rep
9 Input voltage range 120V-160V at half load;160V-280V at full load 210V-280V at half load; 280V-485V at full load Rated frequency 50Hz/60Hz Input f